C Conferentia Proceedings
COB-2015-1971 Energy and Thermal Sciences

Experimental evaluation of thermal behavior of the Rio de Janeiro`s Planetarium

Manoel Antonio da Fonseca Costa Filho1; David Ricardo de Mendonça Soares1; Luis Guilherme Pires de Aragão1

1 Universidade do Estado do Rio de Janeiro

doi:10.20906/CPS/COB-2015-1971

Resumo

This paper aims at carrying out temperature, humidity and global solar radiation measurements inside and outside of the building referred as "Museu do Universo" in the Planetarium of Rio de Janeiro city, in order to evaluate its thermal behavior. The data acquisition system is a programmable logical controller from National Instruments Inc. (NI) named Compact Field Point model cFP-2020, supported by three dedicated signal conditioner boards with 16-bit resolution A/D conversion, which are two NI-RTD-124 boards for 4-wire RTDs connections and a NI-AI-110 analogical input board for receiving the signals from humidity sensors and pyranometers. The supervisory has been developed in NI Labview program, version 8, specifically for this application. It has continuously run, except in some maintenance periods. The supervisory has run in a notebook connected to cFP via a crossover RJ45 cable. The sampling rate was chosen as an instantaneous measurement at each 1 minute. It was 18 simultaneous and continuous measurements at all. Additionally, glazing façade temperatures has been scanned with a Testo 845 infrared thermometer from both its inside and outside surfaces. Temperature measurements of almost all air conditioning supply openings were carried out for verifying homogeneity. The measurements were taken on May, June and July of 2014. The temperature difference among the higher measured point at the top of the domus and conditioned lower floor temperatures has reached around 30°C in some instances. Internal and external glass surfaces have reached, respectively, 60°C and 50°C in a sunny day, and 50°C and 40°C in a completely cloudy day with only incidence of diffuse solar radiation. It was confirmed two different climatic zones: the ground and the second air conditioned floors maintained at around 20°C and the third non conditioned floor including the top of the domus, with a solar heated stagnated air. The heating effect observed from the current glazing façade indicates a great opportunity to energy efficiency actions

Palavras-chave: Thermal Behavior; Hygrothermal; Energy Efficiency; Planetarium; Measured Weather Data

Como citar

Manoel Antonio da Fonseca Costa Filho; David Ricardo de Mendonça Soares; Luis Guilherme Pires de Aragão. “Experimental evaluation of thermal behavior of the Rio de Janeiro`s Planetarium”. 23rd ABCM International Congress of Mechanical Engineering. COBEM2015. 2015. DOI: 10.20906/CPS/COB-2015-1971